+6019-475 8268 / 019-478 8268
sales@dreshler.com.my

Pneumatic Type Level Switch SFP

Previous 10 / 13 Next

Pneumatic Type Level Switch SFP Seojin Contacting Type Measurement Level Measurement


Download Files

SFP.pdf (625.51 KB)
Pneumatic Type Level Switch - SFP


TECHNICAL SPECIFICATIONS:

TYPE Pneumatic Type Level Switch
 
PRINCIPLE A pipe (with its lower part opened) is cut in the length of the electric contact's location, and sealed with a sensor, and then installed; the level of the fluid rises, increasing the pressure in side the pipe, and this water pressure pushes up the expanded diaphragm in the lower sensor, operating the Micro S/W connected to the upper part, for output. It is mostly used for open type fluid tanks that do not have pressure. When a H/L electric contact is required, two sensors are used. The on-off operation static head difference is 20mm. This model also is a unique product of our company.
 
RANGE •Standard : None(on-site Pipe assembly type)
•Optional : Provision of basic 1,000mm pipes (the installed length can be freely adjusted)
 
TEMPERATURE -20¡æ∼80¡æ
 
PRESSURE AMB.
 
FEATURES •On-site detection location adjustment installation
•Best for slurries or high viscosity fluids
•Easy installation
 
OUTPUT •1 SPDT
•Contact capacity : 10A 250V AC
 
APPLICATION •Waste water tank and processing plant
•Sewage processing plant
•Chris, Jam, Ketchup, Food and Beverage tank
•Others
 
REMARKS Mat'l : 304SS, PVC

Please leave your enquiry here, we will reply as soon as possible.
Name*  
Company Name  
Product Interested  
Quantity  
Email*  
Contact No.*  
Attachment  
*only support gif, jpeg, jpg, png, pdf
Messages*  

Switch to Mobile Version
Recent Updates
Subscribe Newsletter